scholarly journals A Review on Fault Current Limiting Devices to Enhance the Fault Ride-Through Capability of the Doubly-Fed Induction Generator Based Wind Turbine

2018 ◽  
Vol 8 (11) ◽  
pp. 2059 ◽  
Author(s):  
Seyed Naderi ◽  
Pooya Davari ◽  
Dao Zhou ◽  
Michael Negnevitsky ◽  
Frede Blaabjerg

The doubly-fed induction generator has significant features compared to the fixed speed wind turbine, which has popularised its application in power systems. Due to partial rated back-to-back converters in the doubly-fed induction generator, fault ride-through capability improvement is one of the important subjects in relation to new grid code requirements. To enhance the fault ride-through capability of the doubly-fed induction generator, many studies have been carried out. Fault current limiting devices are one of the techniques utilised to limit the current level and protect the switches, of the back-to-back converter, from over-current damage. In this paper, a review is carried out based on the fault current limiting characteristic of fault current limiting devices, utilised in the doubly-fed induction generator. Accordingly, fault current limiters and series dynamic braking resistors are mainly considered. Operation of all configurations, including their advantages and disadvantages, is explained. Impedance type and the location of the fault current limiting devices are two important factors, which significantly affect the behaviour of the doubly-fed induction generator in the fault condition. These two factors are studied by way of simulation, basically, and their effects on the key parameters of the doubly-fed induction generator are investigated. Finally, future works, in respect to the application of the fault current limiter for the improvement of the fault ride-through of the doubly-fed induction generator, have also been discussed in the conclusion section.

Author(s):  
Seyed Behzad Naderi ◽  
Pooya Davari ◽  
Dao Zhou ◽  
Michael Negnevitsky ◽  
Frede Blaabjerg

The Doubly-Fed Induction Generator (DFIG) has significant features in comparison with Fixed Speed Wind Turbine (FSWT), which has popularized its application in power system. Due to partial rated back-to-back converters in the DFIG, Fault Ride-Through (FRT) capability improvement is one of the great subjects regarding new grid code requirements. To enhance the FRT capability of the DFIG, many studies have been carried out. Fault current limiting devices as one of the techniques are utilized to limit the current level and protect switches of the back-to-back converter from over-current damage. In this paper, a review is done based on fault current limiting characteristic of the proposed fault current limiting devices Therefore, Fault Current Limiters (FCLs) and Series Dynamic Braking Resistors (SDBRs) are mainly taken into account. Operation of all configurations including their advantages and disadvantages is explained. Impedance type and the fault current limiting devices’ location are two important factors, which significantly affect the DFIG behaviour in the fault condition. These two factors are basically studied by the simulation and their effects on the key parameters of the DFIG are investigated. Finally, future works in respect to the FCL application in the FRT improvement of the DFIG have also been discussed.


2016 ◽  
Vol 31 (6) ◽  
pp. 4935-4944 ◽  
Author(s):  
Shenglong Yu ◽  
Kianoush Emami ◽  
Tyrone Fernando ◽  
Herbert H. C. Iu ◽  
Kit Po Wong

Author(s):  
V. Mohana Kalyani ◽  
J. Preetha Roselyn ◽  
C. Nithya ◽  
D. Devaraj

Due to increasing demand in power, the integration of renewable sources like wind generation into power system is gaining much importance nowadays. The heavy penetration of wind power into the power system leads to many integration issues mainly due to the intermittent nature of the wind and the desirability for variable speed operation of the generators. As the wind power generation depends on the wind speed, its integration into the grid has noticeable influence on the system stability and becomes an important issue especially when a fault occurs on the grid. The protective disconnection of a large amount of wind power during a fault will be an unacceptable consequence and threatens the power system stability. With the increasing use of wind turbines employing Doubly Fed Induction Generator (DFIG) technology, it becomes a necessity to investigate their behavior during grid faults and support them with fault ride through capability. This paper presents the modeling and simulation of a doubly fed induction generator according to grid code compatibility driven by a wind turbine connected to the grid. This paper analyses the voltage sag due to a three-phase fault in the wind connected grid. A control strategy including a crowbar circuit has been developed in MATLAB/SIMULINK to bypass the rotor over currents during grid fault to enhance the fault ride through capability and to maintain system stability. Simulation results show the effectiveness of the proposed control strategies in DFIG based grid connected wind turbine system.