scholarly journals Engineering analysis and development of an advanced technology low cost dry cooling tower heat transfer surface. Interim report, July 1, 1974--January 31, 1976

1976 ◽  
Author(s):  
R.J. Haberski ◽  
R.J. Raco
1980 ◽  
Vol 102 (4) ◽  
pp. 807-812 ◽  
Author(s):  
Ali Montakhab

An analysis of heat exchanger surface geometries for the purpose of reducing dry cooling tower cost is presented. Two sets of results are derived. The first set can be used to evaluate heat transfer surface geometries in an attempt to select those most suitable for dry cooling tower applications. The second set of results can be used to direct research and development efforts toward developing better geometries for dry cooling tower applications. The first set of results is general and is applicable to all heat exchanger surface geometries. The second set is valid only for helical round or continuous fins having smooth, serrated, or cut fins and for staggered and in-line tube arrangements. The methods developed in this paper are not restricted to dry cooling towers per se, but are valid for other applications of fin tube heat exchangers as well.


1981 ◽  
Vol 103 (4) ◽  
pp. 715-719 ◽  
Author(s):  
J. A. Valenzuela ◽  
L. R. Glicksman

A novel design of a rotary heat exchanger to be used as a dry cooling tower is described. The heat exchanger consists of a matrix of thin steel disks which rotate between a hot water bath and a forced draft air stream. On top of the water floats a 2 cm thick layer of oil which coats the rotating disks and thus eliminates evaporation. An analytical model of the heat exchanger was developed and validated with experimental measurements taken on a 1.5 m dia test section. The model was then used to determine the net effect of the oil on the heat transfer performance. Although the oil film that coats the disks presents an additional resistance to the transfer of heat, it also contributes to the heat capacity of the disks. It was found that the reduction in the overall heat transfer rate due to the presence of the oil is small, of the order of 5 to 10 percent.


2013 ◽  
Vol 17 (2) ◽  
pp. 443-455 ◽  
Author(s):  
Hossein Ahmadikia ◽  
Mohsen Soleimani ◽  
Ehsan Gholami

To investigate the effect of water spray and crosswind on the effectiveness of the natural draft dry cooling tower (NDDCT), a three-dimensional model has been developed. Efficiency of NDDCT is improved by water spray system at the cooling tower entrance for high ambient temperature condition with and without crosswind. The natural and forced heat convection flow inside and around the NDDCT is simulated numerically by solving the full Navier-Stokes equations in both air and water droplet phases. Comparison of the numerical results with one-dimensional analytical model and the experimental data illustrates a well-predicted heat transfer rate in the cooling tower. Applying water spray system on the cooling tower radiators enhances the cooling tower efficiency at both no wind and windy conditions. For all values of water spraying rate, NDDCTs operate most effectively at the crosswind velocity of 3m/s and as the wind speed continues to rise to more than 3 m/s up to 12 m/s, the tower efficiency will decrease by approximately 18%, based on no-wind condition. The heat transfer rate of radiator at wind velocity 10 m/s is 11.5% lower than that of the no wind condition. This value is 7.5% for water spray rate of 50kg/s.


2021 ◽  
Vol 188 ◽  
pp. 116628 ◽  
Author(s):  
Yuchen Dai ◽  
Yuanshen Lu ◽  
Alexander Y. Klimenko ◽  
Ying Wang ◽  
Kamel Hooman

Author(s):  
Shuo Li ◽  
M. R. Flynn

AbstractVisible plumes above wet cooling towers are of great concern due to the associated aesthetic and environmental impacts. The parallel path wet/dry cooling tower is one of the most commonly used approaches for plume abatement, however, the associated capital cost is usually high due to the addition of the dry coils. Recently, passive technologies, which make use of free solar energy or the latent heat of the hot, moist air rising through the cooling tower fill, have been proposed to minimize or abate the visible plume and/or conserve water. In this review, we contrast established versus novel technologies and give a perspective on the relative merits and demerits of each. Of course, no assessment of the severity of a visible plume can be made without first understanding its atmospheric trajectory. To this end, numerous attempts, being either theoretical or numerical or experimental, have been proposed to predict plume behavior in atmospheres that are either uniform versus density-stratified or still versus windy (whether highly-turbulent or not). Problems of particular interests are plume rise/deflection, condensation and drift deposition, the latter consideration being a concern of public health due to the possible transport and spread of Legionella bacteria.


2017 ◽  
Vol 112 ◽  
pp. 326-339 ◽  
Author(s):  
Huan Ma ◽  
Fengqi Si ◽  
Yu Kong ◽  
Kangping Zhu ◽  
Wensheng Yan

2018 ◽  
Vol 137 ◽  
pp. 93-100 ◽  
Author(s):  
Weiliang Wang ◽  
Hai Zhang ◽  
Junfu Lyu ◽  
Qing Liu ◽  
Guangxi Yue ◽  
...  

Sign in / Sign up

Export Citation Format