Effect of end distance on the resistance of split ring connectors in timber joints loaded in compression
An experimental program was undertaken to verify the end distance requirements in the Canadian standard for engineering design in wood for split ring connectors in joints loaded in compression. In a laboratory study, 48 joints of the Douglas fir-larch species group using 63 mm diameter split rings, 45 joints of the Douglas fir-larch species group using 102 mm diameter split rings, and 51 joints of the spruce-pine-fir species group using 63 mm diameter split rings were loaded to failure in compression. The split ring end distance varied between 50 and 200 mm for joints with 63 mm diameter split rings and between 80 and 220 mm for joints with 102 mm diameter split rings. Tests were also carried out to verify the cleavage strength of the wood and the strength of the wood in compression parallel-to-grain for each of the specimens. Results show that the end distance does not have any significant effect on the resistance of split ring connectors in joints with members loaded in compression. Key words: split ring, compression, end distance, timber, resistance.