Experimental Study on Flow Evaporation Heat Transfer Characteristics Inside Horizontal Three-Dimensional Enhanced Tubes

Author(s):  
Wei Li ◽  
Chuancai Zhang ◽  
Zhichuan Sun ◽  
Zhichun Liu ◽  
Lianxiang Ma ◽  
...  

Experimental investigation was performed to measure the evaporation heat transfer coefficients of R410A inside three three-dimensional enhanced tubes (1EHT-1, 1EHT-2 and 4LB). The inner and outer enhanced surface of the 4LB tube is composed by arrays of grooves and square pits, while 1EHT-1 tube and 1EHT-2 tube consist of longitudinal ripples and dimples of different depths. All these tubes have an inner diameter of 8.32 mm and an outer diameter of 9.52 mm. Experiment operational conditions are conducted as follows: the saturation temperature is 279 K, the vapor quality ranges from 0.2 to 0.8, and the mass flux varies from 160 kg/(m2·s) to 380 kg/(m2·s). With the mass flux increasing, the heat transfer coefficient increases accordingly. The heat transfer coefficient of 1EHT-2 is the highest of all three tubes, and that of 1EHT-1 is the lowest. The heat transfer coefficient of 4LB ranks between the 1EHT-1 and 1EHT-2 tube. The reason is that the heat transfer areas of the 1EHT-2 and 4LB tube are larger than that of 1EHT-1 and interfacial turbulence is enhanced in 1EHT-2.

2019 ◽  
Vol 142 (1) ◽  
Author(s):  
Weiyu Tang ◽  
Wei Li

Abstract An experimental investigation into heat transfer characteristics during condensation on two horizontal enhanced tubes (EHTs) was conducted. All the tested EHTs s have similar geometries with an outer diameter of 12.7 mm, and a plain tube was also tested for comparison. Investigated enhanced surfaces consist of dimples, protrusions, and grooves, which may produce more flow turbulence and enhanced the liquid drainage effect. The effects of mass fluxes and vapor quality were compared and analyzed. Test conditions were as follows: saturation temperature fixed at 45 °C, mass flux varying from 100 to 200 kg m−2 s−1, and vapor quality ranging from 0.3 to 0.8. The heat transfer coefficient was presented, and the results show that the proposed enhanced surfaces seem to have worse performance than the conventional tubes when the mass flux is less than 150 kg m−2 s−1, while one of the enhanced tubes (2EHT-1) produce an enhanced ratio of 1.03–1.14 when G = 200 kg m−2 s−1. Besides, it was found that the heat transfer coefficient increases with increasing vapor quality, which can be attributed to the increasing diffusion resistance. Mass flux seems to have little effect on the heat transfer performance of smooth tubes, while that of 1EHT increases obviously with increasing mass flux, especially for high vapor qualities.


Author(s):  
Desong Yang ◽  
Zhichuan Sun ◽  
Wei Li

Abstract An experimental investigation of shell-side flow condensation heat transfer was performed on advanced three-dimensional surface-enhanced tubes, including a herringbone micro-fin tube and a newly-developed 1-EHT tube. An equivalent plain tube was also tested for performance comparison. All of the test tubes have similar geometry parameters (inner diameter 11.43mm, outer diameter 12.7mm). Tests were conducted using R410A as the working fluid at a condensation saturation temperature of 45 °C, covering the mass flux range of 10–55 kg/(m2·s) with an inlet quality of 0.8 and an outlet quality of 0.1. Experimental results showed that the plain tube exhibits a better condensation heat transfer performance when compared to the enhanced tubes. Moreover, the mass flux has a significant influence on the heat transfer coefficient for shell-side condensation: the condensation heat transfer coefficient of plain tube decreases when the refrigerant mass flux becomes larger, while the heat transfer coefficient of herringbone tube shows a non-monotonic trend and the heat transfer coefficient of the 1-EHT tube gets higher with increasing refrigerant mass flux. Besides, A new prediction model based on the Cavallini’s equation was developed to predict the condensing coefficient of the three test tubes, and the mean absolute error of the improved equations is less than 4%.


Author(s):  
Xiang Ma ◽  
Wei Li ◽  
Chuan-cai Zhang ◽  
Zhi-chuan Sun ◽  
David J. Kukulka ◽  
...  

Abstract An experimental investigation of condensation and evaporation heat transfer characteristics was performed in 15.88-mm-OD and 12.7-mm-OD smooth and three-dimensional enhanced tubes (1EHT, 3EHT) using R134A and R410A as the working fluid. The enhanced surface of the 1EHT tube is made up of dimples and a series of petal arrays; while the 3EHT tube is made up of rectangular cavities. Evaluations are performed at a saturation temperature of 45 °C, over the quality range of 0.8–0.2 for condensation; while for evaporation the saturation temperature was 6 °C and the quality ranged from 0.2 to 0.8. For condensation, the enhancement ratio (enhanced tube/smooth tube) of the heat transfer coefficients was 1.42–1.95 for the mass flux ranging from 80 to 200 kg/m2s; while for evaporation, the heat transfer enhancement ratio is 1.05–1.42 for values of mass flux that range from 50 to 180 kg/m2s. Furthermore, the 1EHT tube provides the best condensation and evaporation heat transfer performance, for both working fluids at the mass flux considered. This performance is due to the dimples in the enhanced surface that produce interface turbulence; additionally, the increased surface roughness causes additional disturbances and secondary flows near the boundary, producing higher heat fluxes. The main objective of this study was to evaluate the heat transfer enhancement of two enhanced tubes when using R134A and R410A as a function of mass flux, saturation temperature, and tube diameter. As a result of this study, it was determined that the heat transfer coefficient decreases with an increase in saturation temperature and tube diameter.


Author(s):  
Jianghui Zhang ◽  
Yu Guo ◽  
Chuancai Zhang ◽  
Yan He ◽  
David J. Kukulka ◽  
...  

Abstract An experimental investigation of condensation and evaporation heat transfer characteristics was performed in a smooth tube and two enhanced tubes (1EHT, 3EHT) using R134A as refrigerant. All tested tubes have the same inner diameter of 14.68mm and outer diameter of 15.88mm. The enhanced surface of the 1EHT tube is made up by dimples and a series of petal arrays, while that of 3EHT tube is rectangular cavities. The test runs are performed at a saturation temperature of 45°C, over the quality range of 0.8–0.2 for condensation and at a saturation temperature of 6°C, over the quality range of 0.1–0.6 for evaporation. For evaporation, the heat transfer coefficient ratio (hEHT/hs) is approximately 1.2–1.4 for mass from 50–90 kg/m2s. For condensation, the 1EHT tube provides the best condensation heat transfer performance. This is mainly due to the dimples and rectangular cavities that increase heat transfer surface area and interface turbulence, producing additional disturbances, secondary flows near the boundary and flow separation.


Author(s):  
Yu Guo ◽  
Zong-bao Gu ◽  
Zahid Ayub ◽  
Wei Li ◽  
Xiang Ma ◽  
...  

Abstract In this paper, the condensation heat transfer characteristics of R134a inside enhanced tubes using two type of surface structures with different materials was investigated, which were then compared with plain tubes under the same test conditions. The enhanced tubes were: 1EHTa tube with dimpled and petal arrays structure and 1EHTb tube with protrusion and similar petal arrays structure. The experiment was conducted for a mass flux ranging from 100 to 200 kg m−2 s−1 with saturation temperature of 318 K. The inlet and outlet vapor qualities were fixed at 0.8 and 0.2, respectively. The test tubes had the same outer diameter of 12.7 mm. Results showed that the dimpled and protruded surface tubes enhanced the convection condensation heat transfer and the heat transfer coefficient was 1.4 to 1.6 times higher than that of the smooth tube. Heat transfer enhancement of the 1EHTa and 1EHTb tube was mainly due to the complex roughness surface structures that created swirling and increased the interface turbulence. Enhanced tubes exhibited higher performance factors compared to the smooth tube. The average performance factor was 1.3–1.5. As the flow rate increases, there is no significant increase in the condensation heat transfer coefficient. The pressure drop penalty increased with mass flux. Compared with smooth tube, the pressure drop penalty of enhanced tube was larger.


Energies ◽  
2021 ◽  
Vol 14 (19) ◽  
pp. 6325
Author(s):  
Chang-Hyo Son ◽  
Nam-Wook Kim ◽  
Jung-In Yoon ◽  
Sung-Hoon Seol ◽  
Joon-Hyuk Lee

This study investigated the evaporative heat transfer coefficient and pressure drop characteristics of R-1234yf in a horizontal tube with an inner diameter of 6.95 mm under various experimental conditions. The heat transfer coefficient increased with an increase in quality but showed a sharp decrease in the high-quality area. In addition, the heat transfer coefficient increased as the mass flux, heat flux, and saturation temperature increased. Although R-1234yf and R-134a presented similar heat transfer coefficients, that of R-134a was higher. The pressure drop increased with an increase in the quality and mass flux but decreased with an increase in the saturation temperature. The pressure drop of R-134a was larger than that of R-1234yf. In light of the flow pattern diagram by Taitel and Dukler, most of the experiments were included in the annular flow region, and some regions showed intermittent and stratified corrugated flow regions. Kandlikar’s heat transfer coefficient correlation provided the best prediction for the experimental database, with approximately 84% of the predicted data within ±30%. Moreno Quibén and Thome’s equation for pressure drop predicted approximately 88.71% of the data within ±30%.


2020 ◽  
Vol 142 (7) ◽  
Author(s):  
Wei Li ◽  
Yu Guo ◽  
Zong-Bao Gu ◽  
Xiang Ma ◽  
Zahid Ayub ◽  
...  

Abstract In this paper, the condensation heat transfer characteristics of R134a inside enhanced tubes using two types of surface structures with different materials were investigated, which were then compared with plain tubes under the same test conditions. The enhanced tubes were: 1EHTa tube with dimpled and petal arrays structure and 1EHTb tube with protrusion and similar petal arrays structure. The experiment was conducted for a mass flux ranging from 100 to 200 kg m−2 s−1 with saturation temperature of 318.15 K. The inlet and outlet vapor qualities were fixed at 0.8 and 0.2, respectively. The test tubes had the same outer diameter of 12.7 mm. Results showed that the dimpled and protruded surface tubes enhanced the convection condensation heat transfer and the heat transfer coefficient was 1.4–1.6 times higher than that of the smooth tube. Heat transfer enhancement of the 1EHTa and 1EHTb tube was mainly due to the complex roughness surface structures that created swirling and increased the interface turbulence. The condensation heat transfer coefficient increased slightly with increasing mass flux. The pressure drop penalty was found to increase as mass flux increased. Compared with the smooth tube, the pressure drop of Cu-1EHTa tube, SS-1EHTa tube, and Cu-1EHTb tube were 1.15, 1.21, and 1.14 of smooth tube, respectively. Enhanced tubes exhibited higher performance factors (PFs) compared to the smooth tube. The average PF was 1.3–1.5. A new correlation of heat transfer coefficient has been developed within ±15% error band.


Author(s):  
Vijay K. Garg ◽  
Ali A. Ameri

A three-dimensional Navier-Stokes code has been used to compute the heat transfer coefficient on two film-cooled turbine blades, namely the VKI rotor with six rows of cooling holes including three rows on the shower head, and the C3X vane with nine rows of holes including five rows on the shower head. Predictions of heat transfer coefficient at the blade surface using three two-equation turbulence models, specifically, Coakley’s q-ω model, Chien’s k-ε model and Wilcox’s k-ω model with Menter’s modifications, have been compared with the experimental data of Camci and Arts (1990) for the VKI rotor, and of Hylton et al. (1988) for the C3X vane along with predictions using the Baldwin-Lomax (B-L) model taken from Garg and Gaugler (1995). It is found that for the cases considered here the two-equation models predict the blade heat transfer somewhat better than the B-L model except immediately downstream of the film-cooling holes on the suction surface of the VKI rotor, and over most of the suction surface of the C3X vane. However, all two-equation models require 40% more computer core than the B-L model for solution, and while the q-ω and k-ε models need 40% more computer time than the B-L model, the k-ω model requires at least 65% more time due to slower rate of convergence. It is found that the heat transfer coefficient exhibits a strong spanwise as well as streamwise variation for both blades and all turbulence models.


Author(s):  
Jatuporn Kaew-On ◽  
Somchai Wongwises

The evaporation heat transfer coefficients and pressure drops of R-410A and R-134a flowing through a horizontal-aluminium rectangular multiport mini-channel having a hydraulic diameter of 3.48 mm are experimentally investigated. The test runs are done at refrigerant mass fluxes ranging between 200 and 400 kg/m2s. The heat fluxes are between 5 and 14.25 kW/m2, and refrigerant saturation temperatures are between 10 and 30 °C. The effects of the refrigerant vapour quality, mass flux, saturation temperature and imposed heat flux on the measured heat transfer coefficient and pressure drop are investigated. The experimental data show that in the same conditions, the heat transfer coefficients of R-410A are about 20–50% higher than those of R-134a, whereas the pressure drops of R-410A are around 50–100% lower than those of R-134a. The new correlations for the evaporation heat transfer coefficient and pressure drop of R-410A and R-134a in a multiport mini-channel are proposed for practical applications.