Effect of Thermal Storage on the Cooling Capacity of Ambient Sources

Author(s):  
Brian S. Robinson ◽  
M. Keith Sharp

Ambient sources, including ambient air at dry-bulb and wet-bulb temperature, ground temperature and night sky temperature, were evaluated for their potential to provide space cooling in locations across the U.S. While ground temperature is constant beyond a certain depth, the other sources have fluctuating temperatures, which present intermittent potentials for cooling. Simultaneously, cooling demands also fluctuate with outdoor temperature. Thermal storage can bridge intervals of time during which cooling is needed in the building, but ambient source temperature is too high to provide cooling. The duration of these intervals and the thermal storage capacity required to meet cooling needs based on ambient source potential prior to the interval were quantified for all eleven climate zones across the continental U.S using TMY3 weather data. The thermal storage capacity required to meet the entire annual cooling load is dictated by the span of time without ambient source cooling potential that has the greatest ratio of cooling load to ambient source cooling potential prior to the interval. This maximum thermal storage capacity, normalized by building overall loss coefficient, (this ratio has units of time) was one day or less for night sky temperature for all but the three warmest climates. This ratio was one day or less for wet-bulb temperature for four locations, and for dry-bulb temperature for only two locations. Ground temperature provided continuous cooling potential in all but the three warmest climates, where ground temperature was warmer than the indoor comfort temperature. Because the maximum thermal storage capacity was determined in most climates by uncommon and infrequent coincidence of high cooling demand and low ambient source cooling potential, smaller thermal storage provided substantial cooling capacity in most cases. For instance, ten percent of the maximum supplied 99% of the cooling load for the dry-bulb ambient air source in Albuquerque, and 0.1% of the maximum served over 90% of the cooling load with night sky radiation in New Orleans and Phoenix. While considerable development of hardware and control algorithms to utilize ambient sources for space cooling has occurred, this study shows the potential of these sources to further reduce demands for conventional energy for space cooling across a wide range of climates.

Author(s):  
Brian S. Robinson ◽  
M. Keith Sharp

While solar energy provides a source for passive space heating across a variety of climates, other ambient energy sources may be more appropriate for passive space cooling. These ambient resources include ambient air at dry-bulb and wet-bulb temperatures, ground temperature at locations where the soil is cooler than the indoor comfort temperature, and night-sky radiant temperature, which is substantially lower than ambient air in most climates. The focus of this study was on comparing these sources to cooling loads across climates in the US. Using a degree-day approach, annual cooling potentials were calculated for over 800 TMY3 locations. Color-themed maps for each ambient source at several indoor comfort temperature ranges were constructed as visual references for design purposes. In addition, eight US cities (Denver, CO, Los Angeles, CA, Louisville, KY, Madison, WI, Miami, FL, New Orleans, LA, Phoenix, AZ and Washington DC) were selected to represent a range of climate characteristics, including seasonal ambient temperature, diurnal temperature swings, humidity and sky clearness. For each city, an ambient potential to cooling load ratio (ALR) was calculated, with the potential based on an indoor comfort temperature range of 68°F – 72°F and the load calculated with a base temperature of 65°F. ALR, which neglects phase lags between source and load and the associated need for thermal storage, exceeded one for dry-bulb air and for ground temperature for all locations except Miami, New Orleans and Phoenix. Wet-bulb ALR exceeded one for all locations except Miami, and sky ALR exceeded one for all locations. Finally, the effect of limited thermal storage was estimated by calculating daily ambient source fraction, fas, which is the daily ambient cooling potential divided by the daily cooling load. fas thus approximates the cooling potential of systems with one day’s worth of thermal storage, and has an upper limit of one. Fas, the annual sum of fas, equaled one for ground temperature for Los Angeles and Madison and for sky temperature for Denver and Los Angeles. Fas for ground temperature was above 0.9 for all locations except Miami, New Orleans and Phoenix. Fas for sky temperature exceeded 0.6 for all locations. By utilizing all possible combinations of ambient sources, half of the selected locations attained Fas equal to one and the minimum for all locations still exceeded 0.65.


2019 ◽  
Vol 141 (4) ◽  
Author(s):  
M. Adrienne Parsons ◽  
M. Keith Sharp

This study evaluated the building cooling capacity of sky radiation, which was previously identified to have the greatest cooling potential among common ambient sources for climates across the U.S. A heat pipe augmented sky radiator system was simulated by a thermal network with nine nodes, including a thin polyethylene cover with and without condensation, white (zinc oxide) painted radiator plate, condenser and evaporator ends of the heat pipe, thermal storage fluid (water), tank wall, room, sky and ambient air. Heat transfer between nodes included solar flux and sky radiation to cover and plate, wind convection and radiation from cover to ambient, radiation from plate to ambient, natural convection and radiation from plate to cover, conduction from plate to condenser, two-phase heat transfer from evaporator to condenser, natural convection from evaporator to water and from water to tank wall, natural convection and radiation from tank wall to room, and overall heat loss from room to ambient. A thin layer of water was applied to simulate condensation on the cover. Nodal temperatures were simultaneously solved as functions of time using typical meteorological year (TMY3) weather data. Auxiliary cooling was added as needed to limit room temperature to a maximum of 23.9 °C. For this initial investigation, a moderate climate (Louisville, KY) was used to evaluate the effects of radiator orientation, thermal storage capacity, and cooling load to radiator area ratio (LRR). Results were compared to a Louisville baseline with LRR = 10 W/m2 K, horizontal radiator and one cover, which provided an annual sky fraction (fraction of cooling load provided by sky radiation) of 0.855. A decrease to 0.852 was found for an increase in radiator slope to 20 deg, and a drop to 0.832 for 53 deg slope (latitude + 15 deg, a typical slope for solar heating). These drops were associated with increases in average radiator temperature by 0.73 °C for 20 deg and 1.99 °C for 53 deg. A 30% decrease in storage capacity caused a decrease in sky fraction to 0.843. Sky fractions were 0.720 and 0.959 for LRR of 20 and 5, respectively. LRR and thermal storage capacity had strong effects on performance. Radiator slope had a surprisingly small impact, considering that the view factor to the sky at 53 deg tilt is less than 0.5.


Author(s):  
Zachary Springer ◽  
M. Keith Sharp

Ambient energy sources, including ambient air, ground and night sky, have potential for space cooling. The night sky offers the lowest temperature and, therefore, the greatest potential across most of the US. Compared to a previous analysis that considered only the sensible cooling load, the objective of this new project was to evaluate the potential of night-sky radiation (NSR) to also serve the latent cooling load. ASHRAE standard 55 was used to establish the comfort limits (22°C for room temperature and 60% relative humidity). Condensation was evaluated as the mechanism for humidity reduction, thus the dew-point temperature, 13.9°C, corresponding to the ASHRAE limits was the maximum target temperature for night-sky cooling. Typical meteorological year (TMY3) weather data was used for eleven locations representing ASHRAE climate zones. Building heat gain, infiltration/ventilation requirements and night-sky radiator size were characterized by a load-to-radiator ratio LRR defined as the infiltration/ventilation volume flow rate times the ratio of building floor area to radiator area. Three values of LRR were evaluated: 0.35, 3.5 and 35 m/hr. Three thermal storage cases were considered: 1. Annual NSR cooling potential (seasonal storage), 2. Diurnal storage, and 3. The minimum storage capacity to serve the entire annual load, as well as the effects of capacity less than the minimum. To evaluate the effect of night-sky radiator temperature on storage capacity, six NSR temperatures Trad = 13.9 to −26.1°C were tested. Results showed that even in Miami, FL (the most challenging climate evaluated), annual NSR potential exceeded the total sensible and latent cooling load, at least for the lowest LRR and highest Trad. For diurnal storage, NSR could serve less than 20% of the load in the hot and humid southeast, but the entire load in the mountain west. The minimum storage capacity to meet the entire annual load corresponds to the capacity required to bridge the span of time without NSR availability during which the largest cooling load occurs. This capacity decreases with decreasing LRR and decreasing Trad. For the southeast, large capacity is required, but for Louisville, for instance, sufficient capacity is provided by the equivalent of as little as 0.05 m of water over the floor area of the building for LRR = 0.35 m/hr. These results demonstrate that for much of the US, night-sky radiation has the potential to serve the entire annual sensible and latent cooling load.


Author(s):  
Adrienne M. Parsons ◽  
M. Keith Sharp

This study evaluated the building cooling capacity of sky radiation, which was previously identified to have the greatest cooling potential among common ambient sources for climates across the US. [Robinson, et al. 2013b]. A heat pipe augmented sky radiator system was simulated by a thermal network with nine nodes, representing a thin polyethylene cover, white (ZnO) painted radiator plate [Duffie & Beckman 2013], condenser and evaporator ends of the heat pipe, thermal storage fluid (water), tank wall, room, sky and ambient air. Heat transfer between nodes included solar flux and sky radiation to cover and plate, wind convection and radiation from cover to ambient, radiation from plate to ambient, natural convection and radiation from plate to cover, conduction from plate to condenser or, two-phase heat transfer from evaporator to condenser, natural convection from evaporator to water and from water to tank wall, natural convection and radiation from tank wall to room, and overall heat loss from room to ambient. Nodal temperatures were simultaneously solved as functions of time using Typical Meteorological Year (TMY3) weather data. Auxiliary cooling was applied as needed to limit room temperature to a maximum of 23.9°C. For this initial investigation, a moderate climate (Louisville, KY) was used to evaluate the effects of radiator orientation, thermal storage capacity and cooling load to radiator area ratio, LRR. Louisville and two challenging climates (Miami, FL and New Orleans, LA) were then used to evaluate five cover configurations — zero, one and two covers with unconstrained temperature, and zero and one cover with temperature limited to the dew point of ambient air to simulate condensation on the cover. Results were compared to a Louisville baseline with LRR = 10 W/m2K, horizontal radiator and one cover with constrained temperature, which provided an annual sky fraction (fraction of cooling load provided by sky radiation) of 0.861. A decrease to 0.857 was found for an increase in radiator slope to 20°, and a drop to 0.833 for 53° slope (latitude + 15°, a typical slope for solar heating). These drops were associated with increases in average radiator temperature by 0.2°C for 20° and 1.5°C for 53°. A 25% decrease in storage capacity caused a decrease in sky fraction to 0.854. Sky fractions were 0.727 and 0.963 for LRR of 20 and 5, respectively. Sky fractions for the baseline system in Miami and New Orleans were 0.505 and 0.603, respectively. In all three climates, performance was little affected by constraining the cover temperature and by adding a second cover. These results confirm the potential for passive cooling of buildings by radiation to the sky. Climate, LRR and thermal storage capacity had strong effects on performance, while the cover configuration did not. Radiator slope had a surprisingly small impact, considering that the view factor to the sky at 53° tilt is less than 0.5.


2019 ◽  
Vol 141 (4) ◽  
Author(s):  
Zachary Springer ◽  
M. Keith Sharp

The potential of sky radiation (SR) to serve the latent space cooling loads was evaluated. Using ASHRAE standard 55 comfort limits (room temperature 22 °C, relative humidity 60%, and dew-point temperature 13.9 °C), condensation was the chosen mechanism for humidity reduction. Typical meteorological year (TMY3) weather data were used for eleven ASHRAE climate zones. Three values of load-to-radiator ratio (LRR) (infiltration/ventilation volume flow rate times the ratio of building floor area to radiator area) were evaluated: 0.35, 3.5, and 35 m/h. Three thermal storage cases were considered: 1. Annual cooling potential, 2. Diurnal storage, and 3. Minimum storage capacity to serve the entire annual load. Six SR temperatures Trad = 13.9 to −26.1 °C were tested. Even in the most challenging climates, annual SR potential exceeded the total sensible and latent cooling load, at least for the lowest LRR and the highest Trad. For diurnal storage, SR served less than 20% of the load in the hot and humid southeast, but the entire load in the mountain west. The minimum storage capacity to meet the entire annual load decreased with decreasing LRR and decreasing Trad. For the southeast, large capacity was required, but for Louisville, for instance, sufficient capacity was provided by 0.05 m3 of water per m2 of floor area for LRR = 0.35 m/h. These results demonstrate that for much of the U.S., sky radiation has the potential to serve the entire annual sensible and latent cooling load.


Energies ◽  
2021 ◽  
Vol 14 (23) ◽  
pp. 8044
Author(s):  
Ali Pakari ◽  
Saud Ghani

Given the substantial energy use for space cooling in buildings, integrating energy-efficient and sustainable cooling systems into buildings has become increasingly more important. Even though the cooling potential of a near-surface earth-to-air heat exchanger (EAHE) with grass cover was demonstrated in previous studies, the energy savings and environmental benefits resulting from using the EAHE have not yet been quantified. Therefore, in this study, we quantify the energy savings resulting from using a near-surface earth-to-air heat exchanger (EAHE) with grass-covered ground as a precooling unit in hot desert climates. The outlet air conditions of the EAHE during 9 months of the year (March to November), where space cooling is required, are predicted using a 3D transient CFD model, which is validated against field measurements. The EAHE is fabricated from a 1 mm thick aluminum tube with a diameter of 0.15 m and a length of 21.5 m, buried 0.4 m deep. The results showed that the EAHE can cool ambient air by up to 8.5 °C at an air flow rate of 607 m3/h, corresponding to a cooling capacity of 1700 W and a COP of 17. The daily average cooling capacity of the EAHE is about 560 W for an average operation period of 15.1 h per day. When used as a precooling unit for conventional cooling systems, the highest estimated monthly energy savings is 115 kWh, and the estimated annual savings is 741 kWh.


Energies ◽  
2021 ◽  
Vol 14 (15) ◽  
pp. 4675
Author(s):  
Ayat-allah Bouramdane ◽  
Alexis Tantet ◽  
Philippe Drobinski

In this study, we examine how Battery Storage (BES) and Thermal Storage (TES) combined with solar Photovoltaic (PV) and Concentrated Solar Power (CSP) technologies with an increased storage duration and rental cost together with diversification would influence the Moroccan mix and to what extent the variability (i.e., adequacy risk) can be reduced; this is done using recent (2013) cost data and under various penetration scenarios. To do this, we use MERRA-2 climate reanalysis to simulate hourly demand and capacity factors (CFs) of wind, solar PV and CSP without and with increasing storage capabilities—as defined by the CSP Solar Multiple (SM) and PV Inverter Loading Ratio (ILR). We adjust these time series to observations for the four Moroccan electrical zones over the year 2018. Our objective is to maximize the renewable (RE) penetration and minimize the imbalances between RE production and consumption considering three optimization strategies. We analyze mixes along Pareto fronts using the Mean-Variance Portfolio approach—implemented in the E4CLIM model—in which we add a maximum-cost constraint to take into account the different rental costs of wind, PV and CSP. We propose a method to calculate the rental cost of storage and production technologies taking into account the constraints on storage associated with the increase of SM and ILR in the added PV-BES and CSP-TES modules, keeping the mean solar CFs fixed. We perform some load bands-reduction diagnostics to assess the reliability benefits provided by each RE technology. We find that, at low penetrations, the maximum-cost budget is not reached because a small capacity is needed. The higher the ILR for PV, the larger the share of PV in the mix compared to wind and CSP without storage is removed completely. Between PV-BES and CSP-TES, the latter is preferred as it has larger storage capacity and thus stronger impact in reducing the adequacy risk. As additional BES are installed, more than TES, PV-BES is favored. At high penetrations, optimal mixes are impacted by cost, the more so as CSP (resp., PV) with high SM (resp., ILR) are installed. Wind is preferably installed due to its high mean CF compared to cost, followed by either PV-BES or CSP/CSP-TES. Scenarios without or with medium storage capacity favor CSP/CSP-TES, while high storage duration scenarios are dominated by low-cost PV-BES. However, scenarios ignoring the storage cost and constraints provide more weight to PV-BES whatever the penetration level. We also show that significant reduction of RE variability can only be achieved through geographical diversification. Technological complementarity may only help to reduce the variance when PV and CSP are both installed without or with a small amount of storage. However, the diversification effect is slightly smaller when the SM and ILR are increased and the covariances are reduced as well since mixes become less diversified.


Separations ◽  
2021 ◽  
Vol 8 (3) ◽  
pp. 35
Author(s):  
Jason Hoisington ◽  
Jason S. Herrington

A canister-based sampling method along with preconcentrator-Gas chromatography-Mass Spectrometry (GC-MS) analysis was applied to ethylene oxide (EtO or EO) and 75 other volatile organic compounds (VOCs) in ambient air. Ambient air can contain a large variety of VOCs, and thorough analysis requires non-discriminatory sampling and a chromatographic method capable of resolving a complex mixture. Canister collection of whole air samples allows for the collection of a wide range of volatile compounds, while the simultaneous analysis of ethylene oxide and other VOCs allows for faster throughput than separate methods. The method presented is based on US EPA Method TO-15A and allows for the detection of EtO from 18 to 2500 pptv. The method has an average accuracy of 104% and precision of 13% relative standard deviation (RSD), with an instrument run time of 32 min. In addition, a link between canister cleanliness and ethylene oxide growth is observed, and potential mechanisms and cleaning strategies are addressed.


Author(s):  
Wesley R. Bussman ◽  
Charles E. Baukal

Because process heaters are typically located outside, their operation is subject to the weather. Heaters are typically tuned at a given set of conditions; however, the actual operating conditions may vary dramatically from season to season and sometimes even within a given day. Wind, ambient air temperature, ambient air humidity, and atmospheric pressure can all significantly impact the O2 level, which impacts both the thermal efficiency and the pollution emissions from a process heater. Unfortunately, most natural draft process burners are manually controlled on an infrequent basis. This paper shows how changing ambient conditions can considerably impact both CO and NOx emissions if proper adjustments are not made as the ambient conditions change. Data will be presented for a wide range of operating conditions to show how much the CO and NOx emissions can be affected by changes in the ambient conditions for fuel gas fired natural draft process heaters, which are the most common type used in the hydrocarbon and petrochemical industries. Some type of automated burner control, which is virtually non-existent today in this application, is recommended to adjust for the variations in ambient conditions.


Materials ◽  
2021 ◽  
Vol 14 (23) ◽  
pp. 7223
Author(s):  
Marco A. Orozco ◽  
Karen Acurio ◽  
Francis Vásquez-Aza ◽  
Javier Martínez-Gómez ◽  
Andres Chico-Proano

This study presents the energy storage potential of nitrate salts for specific applications in energy systems that use renewable resources. For this, the thermal, chemical, and morphological characterization of 11 samples of nitrate salts as phase change materials (PCM) was conducted. Specifically, sodium nitrate (NaNO3), sodium nitrite (NaNO2), and potassium nitrate (KNO3) were considered as base materials; and various binary and ternary mixtures were evaluated. For the evaluation of the materials, differential Fourier transform infrared spectroscopy (FTIR), scanning calorimetry (DSC), thermogravimetric analysis (TGA), and scanning electron microscopy (SEM) to identify the temperature and enthalpy of phase change, thermal stability, microstructure, and the identification of functional groups were applied. Among the relevant results, sodium nitrite presented the highest phase change enthalpy of 220.7 J/g, and the mixture of 50% NaNO3 and 50% NaNO2 presented an enthalpy of 185.6 J/g with a phase change start and end temperature of 228.4 and 238.6 °C, respectively. This result indicates that sodium nitrite mixtures allow the thermal storage capacity of PCMs to increase. In conclusion, these materials are suitable for medium and high-temperature thermal energy storage systems due to their thermal and chemical stability, and high thermal storage capacity.


Sign in / Sign up

Export Citation Format

Share Document