Simplified models and experimental verification for coupled transmission tower–line system to seismic excitations

2005 ◽  
Vol 286 (3) ◽  
pp. 569-585 ◽  
Author(s):  
Hong-Nan Li ◽  
Wen-Long Shi ◽  
Guo-Xin Wang ◽  
Lian-Guang Jia
2019 ◽  
Vol 19 (06) ◽  
pp. 1950056 ◽  
Author(s):  
Li Tian ◽  
Kunjie Rong ◽  
Kaiming Bi ◽  
Peng Zhang

Failures of transmission tower-line systems have frequently occurred during large earthquakes. It is essential to control the excessive vibrations of transmission tower-line systems to ensure their safe operation in such events. This paper numerically investigates the effectiveness of using a novel bidirectional pounding tuned mass damper (BPTMD) to control the seismic responses of transmission tower-line system when subjected to earthquake ground motions. A finite element model of a typical transmission tower-line system with BPTMD is developed using the commercial software ABAQUS, with the accuracy of the results verified against a previous study. The seismic responses of the system with and without BPTMD are calculated. For comparison, the control effect of using the conventional bidirectional tuned mass damper is also calculated and discussed. Finally, a parametric study is performed to investigate the effects of the mass ratio, seismic intensity, gap size and frequency ratio on the seismic response of the system, while optimal design parameters are obtained.


Author(s):  
Hong-Nan Li ◽  
Wen-Long Shi ◽  
Guo-Xin Wang

The simplified computational models of high-voltage transmission tower-line system under out-of-plane and in-plane vibrations are presented due to seismic excitations in this paper. The equations of motion are derived and the computer program is compiled to obtain the earthquake responses of the coupled system. To verify the rationality of the proposed approaches, the shaking-table experiments of the coupled system of transmission lines and their supporting towers are carried out and the results indicate that the errors of theoretical and testing results of systemic seismic responses are within the acceptable arrange in engineering area. Based on these studies, a simplified analysis method is proposed to make the seismic response calculation of coupled tower-conductor system faster and more effective.


2016 ◽  
Vol 20 (8) ◽  
pp. 1155-1173 ◽  
Author(s):  
Bo Chen ◽  
Shun Weng ◽  
Lunhai Zhi ◽  
Dongming Li

The transmission tower-line system is widely used in electric infrastructures across the world and generally possesses a small stiffness and low structural damping. The excessive vibration of a transmission tower-line system subjected to seismic excitations may induce a structural damage or failure. To avoid the excessive vibration under strong earthquakes, a large transmission tower-line system requires some measures to abate their dynamic responses. Friction damper is a solution to realize the response control of a transmission tower-line system. In this regard, the response mitigation and performance assessment on a transmission tower-line system with friction dampers under strong earthquakes are actively carried out in this study. The analytical model of a transmission line is proposed based on Hamilton’s variational statement of dynamics and Lagrange’s formulation. A two-dimensional lumped mass model of a transmission tower is developed for the dynamic analysis by simplifying the three-dimensional finite element model. The mechanical model of a friction damper is established by considering the effect of damper axial stiffness. The equations of motion and dynamic analytical method of a transmission tower-line system without/with friction dampers subjected to seismic excitations are proposed. In addition, the approach for assessing energy responses of a transmission tower-line system without/with friction dampers subjected to seismic excitations is also developed. A real transmission tower-line system is taken as an example to examine the feasibility of the proposed control approach. The parametric study is conducted to investigate the effects of damper control force, damper stiffness, earthquake intensity, and damper location. The made observations demonstrate that the implementation of friction dampers in a transmission tower-line system can substantially suppress the seismic responses with optimal damper parameters.


2012 ◽  
Vol 06 (04) ◽  
pp. 1250025 ◽  
Author(s):  
TIAN LI ◽  
LI HONGNAN ◽  
LIU GUOHUAN

The effect of multi-component multi-support excitations on the response of power transmission tower-line system is analyzed in this paper, using three-dimensional finite element time-stepping analysis of a transmission tower-line system based on an actual project. Multi-component multi-support earthquake input waves are generated based on the Code for Design of Seismic of Electrical Installations. Geometric non-linearity was considered in the analysis. An extensive parametric study was conducted to investigate the behavior of the transmission tower-line system under multi-component multi-support seismic excitations. The parameters include single-component multi-support ground motions, multi-component multi-support ground motions, the correlations among the three-component of multi-component multi-support ground motions, the spatial correlation of multi-component multi-support ground motions, the incident angle of multi-component multi-support seismic waves, the ratio of the peak values of the three-component of multi-component multi-support ground motions, and site condition with apparent wave velocity of multi-component multi-support ground motions.


2021 ◽  
Vol 9 ◽  
Author(s):  
Jiaxiang Li ◽  
Biao Wang ◽  
Jian Sun ◽  
Shuhong Wang ◽  
Xiaohong Zhang ◽  
...  

Ice shedding causes transmission lines to vibrate violently, which induces a sharp increase in the longitudinal unbalanced tension of the lines, even resulting in the progressive collapse of transmission towers in serious cases, which is a common ice-based disaster for transmission tower-line systems. Based on the actual engineering characteristics of a 500 kV transmission line taken as the research object, a finite element model of a two-tower, three-line system is established by commercial ANSYS finite element software. In the modeling process, the uniform mode method is used to introduce the initial defects, and the collapse caused by ice shedding and its influencing parameters are systematically studied. The results show that the higher the ice-shedding height is, the greater the threat of ice shedding to the system; furthermore, the greater the span is, the shorter the insulator length and the greater the dynamic response of the line; the impact of ice shedding should be considered in the design of transmission towers.


2014 ◽  
Vol 2014 ◽  
pp. 1-10
Author(s):  
Li Tian ◽  
Wenming Wang ◽  
Hui Qian

The effect analysis of strain rate on power transmission tower-line system under seismic excitation is studied in this paper. A three-dimensional finite element model of a transmission tower-line system is created based on a real project. Using theoretical analysis and numerical simulation, incremental dynamic analysis of the power transmission tower-line system is conducted to investigate the effect of strain rate on the nonlinear responses of the transmission tower and line. The results show that the effect of strain rate on the transmission tower generally decreases the maximum top displacements, but it would increase the maximum base shear forces, and thus it is necessary to consider the effect of strain rate on the seismic analysis of the transmission tower. The effect of strain rate could be ignored for the seismic analysis of the conductors and ground lines, but the responses of the ground lines considering strain rate effect are larger than those of the conductors. The results could provide a reference for the seismic design of the transmission tower-line system.