scholarly journals Fault Location Method for DC Distribution Systems Based on Parameter Identification

Energies ◽  
2018 ◽  
Vol 11 (8) ◽  
pp. 1983 ◽  
Author(s):  
Yan Xu ◽  
Jingyan Liu ◽  
Weijia Jin ◽  
Yuan Fu ◽  
Hui Yang

When a short circuit fault occurs on the DC side line, the fault current reaches the peak within a few milliseconds, and the voltage drops significantly. This phenomenon can cause overcurrent flowing through the DC line, semiconductor devices, and AC side, which is a major threat to the operation of the entire system. To solve this problem, this paper proposes a fault location scheme based on parameter identification. Firstly, the entire DC distribution system is regarded as a graph. The intersections of the distribution system lines are regarded as vertices. The current flow of each line is regarded as a directed edge. The network topology matrix is constructed and a fault type recognition algorithm is proposed based on graph theory. Secondly, the mathematical model of the pole-to-pole short-circuit fault and pole-to-ground short-circuit fault are analyzed with double-ended electrical quantities. Transform the fault location problem into a parameter identification problem, four parameters to be identified are extracted, and the fitness function is constructed separately for two kinds of fault cases. Thirdly, a genetic algorithm (GA) is adopted to identify the value of parameters. Considering the fault types, transition resistance and fault location, the Matlab/Simulink simulation platform is used to simulate 18 fault conditions. The simulation results show that the positioning error of the fault location method is less than 1%, which is not affected by the transition resistance and has strong robustness.

Author(s):  
Saeed Zaman Jamali ◽  
Muhammad Omer Khan ◽  
Syed Basit Ali Bukhari ◽  
Muhammad Mehdi ◽  
Gi-Hyeon Gwon ◽  
...  

2014 ◽  
Vol 494-495 ◽  
pp. 1739-1742
Author(s):  
Hong Yu Yang

In China,most of distribution system is neutral noneffectively grounded. And the single-phase fault often happens through cement pole. In this paper,firstly,the voltage of the fault phase and the current of cement pole are derived in 10kV neutral noneffectively grounded distribution systems when cement pole has single-phase ground fault.Secondly,the online fault location method is proposed based on voltage gradient of cement pole.Thirdly,the resistence characristic of cement pole is analyzed and the distance obtained from the gradient voltage of cement pole is given.Finally, the theoretical analysis and simulation experiments show that the method is feasible.


2013 ◽  
Vol 787 ◽  
pp. 902-908 ◽  
Author(s):  
Xin Du ◽  
Min Fang Peng ◽  
Hong Mei Zeng ◽  
Liang Zhu ◽  
Hong Wei Che ◽  
...  

A fault location method based on correlation coefficient was proposed in the paper for the distribution system with distributed generation (DG). At first, by acquiring the Thevenin equivalent parameters of each DG to establish simulation model of the actual distribution network. Then voltage sag feature vectors of each bus would be obtained by simulating short-circuit fault at the location of each bus, respectively. Afterwards, by calculating and analyzing the correlation coefficient between each bus and the actual fault node,, suspicious fault sections can be determined. Finally, the fault section was identified by utilizing the associated node of every suspicious fault section .The method could reduce the fault search range obviously, without a massive requirement of measuring devices, and the required data can be obtained easily. Simulation results of a 10kV distribution network with DG showed that the proposed method was accuracy and effective.


2021 ◽  
Vol 256 ◽  
pp. 01032
Author(s):  
Zhenyu Wang ◽  
Shouxiang Wang ◽  
Qi Liu ◽  
Chunyu Zhang ◽  
Qianyu Zhao ◽  
...  

With the development of power electronic technology, flexible DC distribution system has gradually become a research hotspot. Pole-to-pole short circuit fault is the most serious fault type in DC distribution system. When pole-to-pole short circuit fault occurs in DC side, it will produce a large fault current, which will cause serious harm to DC distribution system. Therefore, it is urgent to install current limiting reactor to limit fault over-current. Aiming at the DC distribution system based on half bridge MMC, this paper analyses the fault mechanism and fault characteristics of pole-to-pole short circuit fault, studies the current limiting effect of the installation position and capacity of current limiting reactor on fault current, and carries out simulation verification in PSCAD / EMTDC platform. The analysis and simulation results show that installing a current limiting reactor at the outlet of the DC side can reduce the peak value of capacitor discharge current, and installing a current limiting reactor at the outlet of the AC side can reduce the overall amplitude of fault current.


2019 ◽  
Vol 11 ◽  
pp. 33-39
Author(s):  
Yury Ya. LYAMETS ◽  
◽  
Mikhail V. MARTYNOV ◽  
Alexander N. MASLOV ◽  
◽  
...  