Objectives for optimization and consequences for operation, design and concept of drinking water treatment plants

2008 ◽  
Vol 8 (3) ◽  
pp. 297-304 ◽  
Author(s):  
A. W. C. van der Helm ◽  
L. C. Rietveld ◽  
Th. G. J. Bosklopper ◽  
J. W. N. M. Kappelhof ◽  
J. C. van Dijk

Optimization for operation of drinking water treatment plants should focus on water quality and not on environmental impact or costs. Using improvement of water quality as objective for optimization can lead to new views on operation, design and concept of drinking water treatment plants. This is illustrated for ozonation in combination with biological activated carbon (BAC) filtration at drinking water treatment plant Weesperkarspel of Waternet, the water cycle company for Amsterdam and surrounding areas. The water quality parameters that are taken into account are assimilable organic carbon (AOC), dissolved organic carbon (DOC) and pathogens. The operational parameters that are taken into account are the ozone dosage and the regeneration frequency of the BAC filters. It is concluded that ozone dosage and regeneration frequency should be reduced in combination with application of newly developed insights in design of ozone installations. It is also concluded that a new concept for Weesperkarspel with an additional ion exchange (IEX) step for natural organic matter (NOM) removal will contribute to the improvement of the disinfection capacity of ozonation and the biological stability of the produced drinking water.

2002 ◽  
Vol 2 (5-6) ◽  
pp. 193-199
Author(s):  
M.J. Yu ◽  
H.M. Cho ◽  
J.Y. Koo ◽  
I.S. Han ◽  
E.M. Gwon ◽  
...  

Recently, Seoul city has tried to modify and upgrade the existing facilities and utilities and to improve the established water treatment plants, instead of application of a new treatment process. These efforts have finally lowered the turbidity of finished water below 0.1NTU. Small lab-scale and pilot-scale experiments have been conducted and they have provided optimum parameters for the design and operation of drinking water treatment plants. In addition, quantitative and/or trace analysis technologies developed for monitoring water quality of effluent from unit processes and automization of facilities, have contributed to the improvement of turbidity in drinking water. The Kueui water treatment plant, one of the drinking water treatment plants in Seoul, produces finished water with 0.08 NTU. It results from the operators' continuous endeavor to lower the turbidity in a scale of 0.01 NTU. The data for 12 months indicated that turbidity of settled water was less than 1.16 NTU and that of filtered water was less than 0.12 NTU for 95% of the period. Sedimentation basins and sand filters satisfy the recommended turbidity criteria, 2 NTU and 0.3 NTU, respectively. Also Kueui water treatment plant has focused on the control of organic matters to decrease in DBPs and on the removal of microorganisms.


2009 ◽  
Vol 9 (3) ◽  
pp. 253-261 ◽  
Author(s):  
A. W. C. van der Helm ◽  
L. T. J. van der Aa ◽  
K. M. van Schagen ◽  
L. C. Rietveld

In general, the available control actions in drinking water treatment plants are not directly related to the process objectives for water quality. Model based optimization of operation of a drinking water treatment plant by direct control of water quality objectives is discussed. Plant control with PID controllers is embedded in the model of a drinking water treatment plant and the ozonation process in the plant is used as a case study. It is concluded that direct control of water quality objectives, e.g. Giardia inactivation for ozonation, can largely reduce uncertainty and variation in process performance and leads to improvements of drinking water quality. In the discussed case it led to less bromate formation at the same disinfection capacity. Embedded plant control with PID controllers in the model of drinking water treatment plants through the use of code for writing control functionality has a large potential for model based optimization of operation.


2009 ◽  
Vol 9 (4) ◽  
pp. 379-386 ◽  
Author(s):  
S. A. Baghoth ◽  
M. Dignum ◽  
A. Grefte ◽  
J. Kroesbergen ◽  
G. L. Amy

For drinking water treatment plants that do not use disinfectant residual in the distribution system, it is important to limit availability of easily biodegradable natural organic matter (NOM) fractions which could enhance bacterial regrowth in the distribution system. This can be achieved by optimising the removal of those fractions of interest during treatment; however, this requires a better understanding of the physical and chemical properties of these NOM components. Fluorescence excitation-emission matrix (EEM) and liquid chromatography with online organic carbon detection (LC-OCD) were used to characterize NOM in water samples from one of the two water treatment plants serving Amsterdam, The Netherlands. No disinfectant residual is applied in the distribution system. Fluorescence EEM and LC-OCD were used to track NOM fractions. Whereas fluorescence EEM shows the reduction of humic-like as well as protein-like fluorescence signatures, LC-OCD was able to quantify the changes in dissolved organic carbon (DOC) concentrations of five NOM fractions: humic substances, building blocks (hydrolysates of humics), biopolymers, low molecular weight acids and neutrals.


2013 ◽  
Vol 6 (1) ◽  
pp. 1-10 ◽  
Author(s):  
A. Grefte ◽  
M. Dignum ◽  
E. R. Cornelissen ◽  
L. C. Rietveld

Abstract. To guarantee a good water quality at the customers tap, natural organic matter (NOM) should be (partly) removed during drinking water treatment. The objective of this research was to improve the biological stability of the produced water by incorporating anion exchange (IEX) for NOM removal. Different placement positions of IEX in the treatment lane (IEX positioned before coagulation, before ozonation or after slow sand filtration) and two IEX configurations (MIEX® and fluidized IEX (FIX)) were compared on water quality as well as costs. For this purpose the pre-treatment plant at Loenderveen and production plant Weesperkarspel of Waternet were used as a case study. Both, MIEX® and FIX were able to remove NOM (mainly the HS fraction) to a high extent. NOM removal can be done efficiently before ozonation and after slow sand filtration. The biological stability, in terms of assimilable organic carbon, biofilm formation rate and dissolved organic carbon, was improved by incorporating IEX for NOM removal. The operational costs were assumed to be directly dependent of the NOM removal rate and determined the difference between the IEX positions. The total costs for IEX for the three positions were approximately equal (0.0631 € m−3), however the savings on following treatment processes caused a cost reduction for the IEX positions before coagulation and before ozonation compared to IEX positioned after slow sand filtration. IEX positioned before ozonation was most cost effective and improved the biological stability of the treated water.


2020 ◽  
Vol 20 (6) ◽  
pp. 2106-2118
Author(s):  
Kassim Chabi ◽  
Jie Zeng ◽  
Lizheng Guo ◽  
Xi Li ◽  
Chengsong Ye ◽  
...  

Abstract People in remote areas are still drinking surface water that may contain certain pollutants including harmful microorganisms and chemical compounds directly without any pretreatment. In this study, we have designed and operated a pilot-scale drinking water treatment unit as part of our aim to find an economic and easily operable technology for providing drinking water to people in those areas. Our small-scale treatment unit contains filtration and disinfection (UV–C irradiation) stages to remove pollutants from source water. The water quality index was determined based on various parameters such as pH, temperature, dissolved oxygen, nitrate, nitrite, ammonium, phosphorus, dissolved organic carbon and bacteria. Water and media samples after DNA extraction were sequenced using Illumina MiSeq throughput sequencing for the determination of bacterial community composition. After the raw water treatment, the reduction of bacteria concentration ranged from 1 to 2 log10. The average removal of the turbidity, ammonium, nitrite, phosphorus and dissolved organic carbon reached up to 95.33%, 85.71%, 100%, 28.57%, and 45%, respectively. In conclusion, multiple biological stages in our designed unit showed an improvement of the drinking water quality. The designed drinking treatment unit produces potable water meeting standards at a lower cost of operation and it can be used in remote areas.


2019 ◽  
Vol 24 (1) ◽  
pp. 135-163
Author(s):  
Jader Martínez Girón ◽  
Jenny Vanessa Marín-Rivera ◽  
Mauricio Quintero-Angel

Population growth and urbanization pose a greater pressure for the treatment of drinking water. Additionally, different treatment units, such as decanters and filters, accumulate high concentrations of iron (Fe) and manganese (Mn), which in many cases can be discharged into the environment without any treatment when maintenance is performed. Therefore, this paper evaluates the effectiveness of vertical subsurface wetlands for Fe and Mn removal from wastewater in drinking water treatment plants, taking a pilot scale wetland with an ascending gravel bed with two types of plants: C. esculenta and P. australis in El Hormiguero (Cali, Colombia), as an example. The pilot system had three upstream vertical wetlands, two of them planted and the third one without a plant used as a control. The wetlands were arranged in parallel and each formed by three gravel beds of different diameter. The results showed no significant difference for the percentage of removal in the three wetlands for turbidity (98 %), Fe (90 %), dissolved Fe (97 %) and Mn (98 %). The dissolved oxygen presented a significant difference between the planted wetlands and the control. C. esculenta had the highest concentration of Fe in the root with (103.5 ± 20.8) µg/g ; while P. australis had the highest average of Fe concentrations in leaves and stem with (45.7 ± 24) µg/g and (41.4 ± 9.1) µg/g, respectively. It is concluded that subsurface wetlands can be an interesting alternative for wastewater treatment in the maintenance of drinking water treatment plants. However, more research is needed for the use of vegetation or some technologies for the removal or reduction of the pollutant load in wetlands, since each drinking water treatment plant will require a treatment system for wastewater, which in turn requires a wastewater treatment system as well.


2019 ◽  
Vol 19 (8) ◽  
pp. 2330-2337
Author(s):  
Susumu Hasegawa ◽  
Yasuhiro Tanaka ◽  
Naokazu Wake ◽  
Ryosuke Takagi ◽  
Hideto Matsuyama

Abstract Recently, membrane filtration systems have become increasingly common in drinking water treatment plants. In this industry, preventing membrane fouling is of utmost importance. Many studies on the relationship between raw water components and membrane fouling have been performed in laboratory conditions. However, very few studies have analyzed the components of foulants on the fouled membrane as operated in actual drinking water treatment plants. By analyzing these components in plant-conditions, membrane fouling will be more effectively prevented. In this study, we analyzed the components of foulants extracted with 0.1 N NaOH from a fouled membrane operated in a drinking water treatment plant in Japan. Our analysis revealed that the main foulants were humic substances. In order to dissolve the accumulated humic substances, additional chemical cleaning was attempted with 500 ppm sodium hypochlorite. As a result, it was found that humic substances were dissolved and filtration resistance significantly decreased. Additionally, the removal of inorganic foulants was also greater after chemical cleaning with 500 ppm sodium hypochlorite, as inorganic foulants trapped within humic substances were released to the membrane surface as hydroxides by the additional sodium hypochlorite cleaning and were dissolved by the periodic citric acid cleaning.


2019 ◽  
Vol 19 (7) ◽  
pp. 2098-2106
Author(s):  
Chelsea W. Neil ◽  
Yingying Zhao ◽  
Amy Zhao ◽  
Jill Neal ◽  
Maria Meyer ◽  
...  

Abstract Source water quality can significantly impact the efficacy of water treatment unit processes and the formation of chlorinated and brominated trihalomethanes (THMs). Current water treatment plant performance models may not accurately capture how source water quality variations, such as organic matter variability, can impact treatment unit processes. To investigate these impacts, a field study was conducted wherein water samples were collected along the treatment train for 72 hours during a storm event. Systematic sampling and detailed analyses of water quality parameters, including non-purgeable organic carbon (NPOC), UV absorbance, and THM concentrations, as well as chlorine spiking experiments, reveal how the THM formation potential changes in response to treatment unit processes. Results show that the NPOC remaining after treatment has an increased reactivity towards forming THMs, and that brominated THMs form more readily than chlorinated counterparts in a competitive reaction. Thus both the reactivity and quantity of THM precursors must be considered to maintain compliance with drinking water standards, a finding that should be incorporated into the development of model-assisted treatment operation and optimization. Advanced granular activated carbon (GAC) treatment beyond conventional coagulation–flocculation–sedimentation processes may also be necessary to remove the surge loading of THM-formation precursors during a storm event.