Energy Efficiency Analyses and Comparison of Air and Water Cooled High Performance Servers

Author(s):  
Michael J. Ellsworth ◽  
Madhusudan K. Iyengar

This paper presents a study that illustrates the energy efficiency benefits of using water cooling for server thermal management versus utilizing air-cooling for high performance server applications. In 2008 IBM introduced the water cooled Power 575 Supercomputing Node, which is packaged in a super-dense 2U (88.9 mm) form factor. A fully configured system can dissipate as much as 72 kW with 80% of the heat load going to water. A fully air cooled version of this system, developed by Hitachi, operates 3.5 GHz and dissipates 61 kW at the frame level. In this paper, numerical analyses is first carried to help provide a context for the data center air-conditioning energy consumption, necessary to cool comparable performance clusters for both the air and water cooled racks, respectively. The room level CFD calculations are then extended to the facility level, by including the energy consumption of the refrigeration chiller, the building and condenser water pumps, and the cooling towers. Recent innovations that enable the use of water side economizers as well as 100% water cooling of racks are also discussed. The results show that there can be as much as a 45% reduction in the facilities power to cool the water cooled system compared to the energy required for the air cooled equivalent. When 100% of the server heat load is transferred directly to the chilled water supplied to the racks, there can be a 50% energy savings compared to traditional air-cooling. Lastly, use of 100% water cooling in conjunction with water side economizers can yield more than 90% cooling energy savings compared to the air-cooled configurations.

2020 ◽  
Vol 142 (3) ◽  
Author(s):  
Zhi Hu Xue ◽  
Wei Qu ◽  
Ming Hui Xie

Abstract Two high performance loop heat pipes (LHPs) are developed for direct cooling of the chips in supercomputer. The two LHPs using flat evaporator are: one called water-cooling LHP and another one called air-cooling LHP. The working fluid of LHP is ammonia. The water-cooling LHP can work well at a heat load up to 663 W and air-cooling LHP can work well at a heat load up to 513 W. The two LHPs applying to the real computer servers are realized and tested. The server test results with water-cooling LHP have shown that the operating temperature of central processing units (CPUs) can be controlled to about 67 °C to ensure the reliable operating and acceptable level for electronic chips, even at condenser-cooling water temperature of 40 °C with low water flowrate of 0.055 m3/h. The server test results with air-cooling LHP have shown that the operating temperature of CPUs can be controlled to about 51 °C even at condenser-cooling wind temperature of 30 °C with wind flowrate of 41.88 m3/h.


2008 ◽  
pp. 55-61 ◽  
Author(s):  
Bojana Prodanic ◽  
Aleksandar Jokic ◽  
Jelena Markovic ◽  
Zoltan Zavargo

General trend of free trade at the regional level as well as in the direction of European Union has motivated sugar factories located in Serbia to invest into technologies that are more efficient in order to make their products more competitive in the markets of Europe. Until 2005, the project of energy efficiency improvement in Serbian sugar factories was conducted in Crvenka and Zabalj. Now, they have energy consumption around 1 MJ/kg beet, in contrast to the previous consumption of 1.2 up to 1.5 MJ/kg beet. Further improvements are possible but investments would be high. A result of measurements taken during 2006, after the sugar factory "Donji Srem" - Pecinci was reconstructed showed that a considerable saving has been achieved. The first set of measurements showed that the energy consumption was 1.01 MJ/kg beet, which was 20% higher than intended, but at the same time energy savings were about 30% lower with respect to the values before the reconstruction.


Membranes ◽  
2021 ◽  
Vol 11 (10) ◽  
pp. 781
Author(s):  
Federico Leon ◽  
Alejandro Ramos ◽  
S. Ovidio Perez-Baez

This article shows the optimization of the reverse osmosis process in seawater desalination plants, taking the example of the Canary Islands, where there are more than 320 units of different sizes, both private and public. The objective is to improve the energy efficiency of the system in order to save on operation costs as well as reduce the carbon and ecological footprints. Reverse osmosis membranes with higher surface area have lower energy consumption, as well as energy recovery systems to recover the brine pressure and introduce it in the system. Accounting for the operation, maintenance and handling of the membranes is also important in energy savings, in order to improve the energy efficiency. The energy consumption depends on the permeate water quality required and the model of the reverse osmosis membrane installed in the seawater desalination plant, as it is shown in this study.


2014 ◽  
Vol 655 ◽  
pp. 15-20 ◽  
Author(s):  
Sven Kreitlein ◽  
Tobias Rackow ◽  
Jörg Franke

This paper introduces a method for the assessment and evaluation of energy efficiency of the manufacturing processes in the production as well as a corporate and cross-industry comparison. Already today, energy-related characteristic value systems are used, which are related to the energy consumption of large electronic household appliances or are focusing on their production facilities. The energy efficiency value is a newly developed indicator and will provide valuable information about the energy efficiency of the production of various products, production operators, and consumers. In the following, the energy efficiency value, which is based on the approach of minimal value calculation, is presented in detail. The basic idea is the comparison and evaluation of energy efficiency based on the ratio of the theoretically required energy consumption to the actual energy consumption. Depending on the analysis of influencing factors, a model highlighting their dependencies could be established. The developed system hinges on a successive calculation of the minimum value. Each of these minimum types can be put in relation to the measured energy consumption. However, depending on the chosen basis, the conclusion and focus of the calculated key figure may vary. By using the real minimum as a basis, the actually existing energy savings become visible. The method will be put to the test through an exemplary application for processes in the fields of cutting technologies. This course of action allows for the validation of the developed energy efficiency value and reveals the potential of this method.


Author(s):  
Pawel Olszewski ◽  
Claus Borgnakke

The aim of this research is to estimate the influence of compressed air volumetric capacity on the energy consumption in systems equipped with oil-lubricated screw compressors. A mathematical model of oil-lubricated screw compressors has been proposed. The model is verified by comparing with real measurements, and overall uncertainty analysis is estimated. An in-house developed numerical code (c++) is used to calculate the energy consumption in 252,000 combinations. The final result can be used to estimate the energy efficiency of existing air systems and to assess potential energy savings due to changes in the operation of the system and its control strategy.


Energies ◽  
2018 ◽  
Vol 11 (8) ◽  
pp. 2166 ◽  
Author(s):  
Aniela Kaminska ◽  
Andrzej Ożadowicz

Energy used for lighting is one of the major components of total energy consumption in buildings. Nowadays, buildings have a great potential to reduce their energy consumption, but to achieve this purpose additional efforts are indispensable. In this study, the need for energy savings evaluation before the implementation of lighting control algorithms for a specified building is highlighted. Therefore, experimental tests have been carried out in a university building with laboratories and other rooms, equipped with KNX building automation system. A dimmable control strategy has been investigated, dependent on daylight illuminance. Moreover, a relationship between external and internal daylight illuminance levels has been evaluated as well. Based on the experimental results, the authors proposed a method for the rough estimation of electrical energy savings. Since, according to the EN 15232 standard, Building Automation and Control Systems (BACS) play an important role in buildings’ energy efficiency improvements, the BACS efficiency factors from this standard have been used to verify the experimental results presented in the paper. The potential to reduce energy consumption from lighting in non-residential buildings by 28% for offices and 24% for educational buildings has been confirmed, but its dependence on specific building parameters has been discussed as well.


Energies ◽  
2019 ◽  
Vol 12 (9) ◽  
pp. 1816 ◽  
Author(s):  
Kwan Byum Maeng ◽  
Jiyeon Jung ◽  
Yoonmo Koo

The building sector is considered to be important for Korean energy issues as it accounts for approximately 20% of Korea’s final energy consumption. As one of Korea’s passive strategies in its emission reduction plan is reducing energy consumption through improvements in energy efficiency because the energy loss mostly occurs from window sets, this study aims to examine the preferences and role of the energy efficiency level of window sets in South Korea. Given that the lifespan of a building exceeds 20 years, a building’s energy efficiency significantly impacts accumulated energy savings. However, window sets affect not only energy efficiency, but also the interior appearance of the building; therefore, it is important to understand consumer preferences and to examine their effect on building energy reduction accordingly. Using a mixed logit model, this study analyzes window set preferences and energy savings. As a result, this study determines that consumers consider the energy efficiency level to be the second most important factor in determining window preference, following the cost of the window. In addition, this study found that the marginal willingness to pay for efficiency level 2 window sets compared to level 3 window sets is USD 1256. For level 1 window sets, this figure increases to USD 3140. Further, a scenario analysis is conducted to analyze the government incentive program’s effectiveness in encouraging consumers to purchasing higher energy efficiency more efficient products, and thus in promoting the eco-friendly consumption of in households. Taking into consideration of households’ willingness to pay and cost saving amount for using energy efficient window sets, the optimal value of government incentives of is found to be approximately USD 700 is found to be optimal.


2020 ◽  
Vol 81 (5) ◽  
pp. 876-890
Author(s):  
John N. Zvimba ◽  
Eustina V. Musvoto

Abstract About 55% of energy used in the South African water cycle is for wastewater treatment, with the bulk of this energy associated with aeration in biological processes. However, up to 15% of wastewater energy demand can be offset by energy generation from sludge (power and/or combined heat and power), while best practices adoption can deliver energy efficiency gains of between 5% and 25% in the water cycle. Advanced process modelling and simulation has been applied in this study as a tool to evaluate optimal process and aeration control strategies. This study further applied advanced modelling to investigate and predict the potential energy consumption and consumption cost pattern by the South African wastewater sector resulting from implementation of optimal process and aeration energy use reduction strategies in support of sustainable municipal wastewater management. Aeration energy consumption and cost savings of 9–45% were demonstrated to be achievable through implementation of energy conservation measures without compromising final effluent regulatory compliance. The study further provided significant potential future energy savings as high as 50% and 78% through implementation of simple and complex aeration energy conservation measures respectively. Generally, the model-predicted energy savings suggest that adoption of energy efficiency should be coupled with electricity generation from sludge in order to achieve maximum energy consumption and cost savings within the South African wastewater services sector.


2019 ◽  
Vol 8 (1) ◽  
Author(s):  
Salah M Alabani ◽  
Ibrahim H Tawil

The residential sector in Libya has grown over the past decade in the construction of residential buildings due to the increase in the population. Moreover, the increase in the level of income has contributed to the increase in the purchase of household appliances, which leads to increased demand for energy. Energy consumption in the household sector accounted for 31% of total energy consumption during 2010, and the share of air conditioners in this sector consumed 18.35%. To reduce energy consumption and improve energy efficiency in this sector, policies should be considered to apply energy efficiency standards and markers to household electrical appliances, as they are considered one of the most successful programs used in the world. Countries are implementing such programs to reduce energy consumption in the domestic sector. This paper presents the possibility of implementing such programs to introduce the importance of energy efficiency standards and labeling programs for home appliances in Libya. The calculations required to design such programs show the energy savings that can be achieved during cooling loads in the summer period of 4 months July, August, September). A strategic plan has been developed during 10-year (2020-2030) to estimate the expected savings of energy consumed and to identify possible obstacles and difficulties by gradually increasing the energy efficiency ratio for comestic air conditioners in two stages, from EER10 to EER11 in the first stage is then raised to EER12 as the second stage.


Author(s):  
Ganesh Doiphode ◽  
Hamidreza Najafi ◽  
Mariana Migliori Favaretto

Abstract Buildings are one of the largest energy consumers in the United States. K-12 schools are responsible for nearly 8% of energy consumption by commercial buildings which is equivalent to 1.44% of total annual energy consumption in the country. Understanding the baseline energy consumption of the schools as well as identifying effective energy efficiency measures (EEMs) that result in significant energy savings without compromising occupant’s comfort in a given climate condition are essential factors in moving towards a sustainable future. In a collaboration between Florida Institute of Technology and Brevard Public Schools, three schools are identified for a test study in Melbourne, FL, representing the humid subtropical climate. Energy audit is conducted for these schools and monthly utility bill data as well as background information, end-user’s data and their associated operating schedules are obtained. A detailed analysis is performed on the utility bill data and energy consumption by each end-user is estimated. Several EEMs are considered and evaluated to achieve an improved energy efficiency for the schools. The implementation cost of each EEM and the associated simple payback period is also determined. A study is also conducted to explore possibility of using solar power to cover 50% of energy requirements of each school and the cost and payback period of the project are evaluated. The results of this paper provide insights regarding prioritizing energy efficiency projects in K-12 schools in humid subtropical climates and particularly the state of Florida and help with decision making regarding investment in on-site power generation using solar energy.


Sign in / Sign up

Export Citation Format

Share Document