A Reconfigureable Passive Solar Test Facility

Author(s):  
Brian S. Robinson ◽  
M. Keith Sharp

A 12′ by 24′ passive solar test building has been constructed on the campus of the University of Louisville. The building envelope is comprised of structural insulated panels (SIPs), 12″ thick, (R-value of 45 ft2F/Btu) for the floor and walls and 16″ (R-63) for the roof. The building is divided into two symmetrical rooms with a 12″ SIPs wall separating the rooms. All joints between panels are caulked to reduce infiltration. Each room contains one window (R-9) on the north side wall, and two windows (also R-9) facing south for ventilation and daylighting, but which will also provide some direct gain heating. The south wall of each room features an opening that will accommodate a passive solar heating system so that performance of two systems can be compared side-by-side. The overhang above the south openings is purposely left short to accommodate an awning to provide adjustable shading. The calculated loss coefficient (UA) for each room of the building is 6.07 W/K. Each room is also equipped with a data acquisition system consisting on an SCXI 1600 16 bit digitizer and an SCXI 1102B isolation amplifier with an SCXI 1303 thermocouple module. Pyranometers are placed on the south wall and the clerestory wall to measure insolation on the solar apertures. For initial tests, one room is equipped with an original heat pipe system previously tested in another building, while the other is equipped with a modified heat pipe system. Changes to the modified system include copper absorbers versus aluminum, an adiabatic section constructed of considerably less thermally-conductive DPM rubber than the copper used for the original design, and one of the five condenser sections of the heat pipes is exposed directly to the room air to provide early-morning heating. Experimental results will be compared to simulations with as-built building characteristics and actual weather data. Previous simulations with a load to collector ratio of 10 W/m2K, a defined room comfort temperature range between 65°F to 75°F, and TMY3 weather data for Louisville, KY, showed that the modified heat pipe wall design improves annual solar fraction by 16% relative to the original design.

Author(s):  
Brian S. Robinson ◽  
M. Keith Sharp

Thermal performance of an improved passive solar heat pipe system was directly compared to that of a previous prototype. Simulated and experimental results for the first prototype established baseline performance. Subsequently, potential improvements were simulated, and a second prototype was built and tested along side the first. The system uses heat pipes for high rates of heat transfer into the building, and limited losses in the reverse direction. The evaporator section of each heat pipe is attached to a glass-covered absorber on the outside of a south wall, and the slightly elevated condenser section is either immersed in water in a thermal storage tank or exposed to air in the room. Two-phase flow occurs in the heat pipe only when the evaporator is warmer than the condenser, creating a thermal diode effect. Computer simulations showed that system performance could be improved by using thicker insulation between the absorber and the storage tanks, and by switching from a copper to a rubber adiabatic section, which both reduced heat losses to ambient from the storage tanks. Early morning heating was improved by exposing one of five condensers directly to room air, which also improved overall system efficiency. A copper solar absorber soldered to the copper evaporator section improved heat conduction compared to the previous aluminum absorber bonded to the copper evaporator. Together these modifications improved simulated annual solar fraction by 20.8%. The new prototype incorporating these changes was tested along side the previous prototype in a two-room passive solar test facility during January through February of 2013. Temperatures were monitored with thermocouples at multiple locations throughout the systems, in each room and outdoors. Insolation was measured by four pyranometers attached to the building. Results showed that the design modifications implemented for the new model increased thermal gains to storage and to the room, and decreased thermal losses to ambient. The load-to-collector ratio for the experiments was 2.7 times lower than for the simulations, which decreased the potential for experimental improvements compared to the simulated improvements. However, average daily peak efficiency for the new system was 85.0%, compared to 80.7% for the previous system. Furthermore, the average storage temperature over the entire testing period for the new model was 13.4% higher than that of the previous model, while the average room temperature over the same period was 24.6% greater for the new system.


Author(s):  
Logan S. Poteat ◽  
M. Keith Sharp

The Solar Load Ratio (SLR) method is a performance prediction algorithm for passive solar space heating systems developed at Los Alamos National Laboratory. Based on curve fits of detailed thermal simulations of buildings, the algorithm provides fast estimation of monthly solar savings fraction for direct gain, indirect gain (water wall and concrete wall) and sunspace systems of a range of designs. Parameters are not available for passive solar heat pipe systems, which are of the isolated gain type. While modern computers have increased the speed with which detailed simulations can be performed, the quick estimates generated by the SLR method are still useful for early building design comparisons and for educational purposes. With this in mind, the objective of this project was to develop SLR predictions for heat pipe systems, which use heat pipes for one-way transport of heat into the building. A previous thermal network was used to simulate the heat pipe system with Typical Meteorological Year (TMY3) weather data for 13 locations across the US, representing ranges of winter temperature and available sunshine. A range of (nonsolar) load-to-collector ratio LCR = 1–15 W/m2K was tested for each location. The thermal network, along with TMY3 data, provided monthly-average-daily absorbed solar radiation and building load to calculate SLR. Losses from the solar aperture in a heat pipe system are very low compared to conventional passive solar systems, thus the load-to-collector ratio of the solar aperture was neglected in these preliminary calculations. Likewise, nighttime insulation is unnecessary for a heat pipe system, and was not considered. An optimization routine was used to determine an exponential fit (the heart of the SLR method) to simulated monthly solar savings fraction (SSF) across all locations and LCR values. Accuracy of SSF predicted by SLR compared to the thermal network results was evaluated. The largest errors (up to 50%) occurred for months with small heating loads (< 80 K days), which inflated SSF. Limiting the optimization to the heating season (October to March), reduced the error in SSF to an average of 4.24% and a standard deviation of 5.87%. These results expand the applications of the SLR method to heat pipe systems, and allow building designers to use this method to estimate the thermal benefits of heat pipe systems along with conventional direct gain, indirect gain and sunspace systems.


Author(s):  
Brian S. Robinson ◽  
M. Keith Sharp

The heat pipe augmented solar heating system significantly reduces heating loads relative to other conventional passive space heating systems [1–3]. Yet unwanted thermal gains during the cooling season from passive solar systems increase cooling loads and, in extreme cases, may even increase overall space conditioning loads relative to a nonsolar building. The objective of this study was to compare the effectiveness of several design modifications and control strategies for the heat pipe wall to reduce unwanted gains. MATLAB was used to simulate four different unwanted gains reduction mechanisms: 1. shading to block beam radiation from striking the collector, 2. an opaque cover to block all radiation from striking the collector, 3. a mechanical valve in the adiabatic section to eliminate convective heat transfer through the heat pipe into the room, and 4. switching the elevations of the evaporator and condenser sections of the heat pipe to provide heat transfer out of the room during the cooling season. For each mechanism, three different control strategies were evaluated: 1. Seasonal control, for which the prescribed mechanism is deployed at the beginning and removed at the end of the cooling season, 2. ambient temperature-based control, for which the mechanism is deployed if the forecast for the next hour (based on TMY3 weather data) is greater than 65°F, and 3. room temperature-based control, for which the mechanism is deployed if auxiliary cooling was required for the previous hour. For the seasonal strategy, the months for which the unwanted gains reduction mechanism should be deployed to minimize overall space conditioning loads were estimated with a season determination ratio (SD), defined as the monthly ratio of unwanted gains to heating load. Results suggested that SD may be a ‘universal’ parameter that can be applied across a range of climates for quick assessment of its optimal cooling season. With TMY3 data for Louisville, KY, the heat pipe system performed best with ambient temperature-based control. The mechanical valve was the best single mechanism. While in many cases the combination of the valve with a cover or shading produced slightly better performance than the mechanical valve alone, these additional reductions were small. Switching elevations of the evaporator and condenser sections produced little cooling, because of the low thermal emittance of the absorber and low thermal transmittance of the cover, and for the Louisville climate, small diurnal temperature swings during the summer.


Author(s):  
Brian S. Robinson ◽  
Michael V. Albanese ◽  
Nick Chmielewski ◽  
Ellen G. Brehob ◽  
M. Keith Sharp

The focus of this project is on simulation and testing of a novel passive solar heating system that utilizes the one-way heat transfer of heat pipes to significantly improve heating performance relative to conventional passive solar systems. A set of programmed thermal networks were used to simulate the performance of several conventional passive solar heating systems, including direct gain, concrete wall indirect gain and water wall indirect gain, and the heat pipe system. Simulations performed for four US locations representing a range of winter temperatures and available insolation exhibited higher performance for the heat pipe system, particularly in cold climates with low insolation. A small-scale laboratory model was constructed and tested under controlled conditions to confirm simulated system component performance and to test a range of component variations. Measured system efficiency was 85.1 ± 0.72%. A full-scale prototype was constructed, installed and instrumented. Results from a 21-day period in April show a prototype thermal efficiency range from 60–75% and an average of 66.2%; and a 30-day period in October and November ranges from 60–85% with an average of 73.9%. An opaque cover over the prototype, periodically installed to minimize unwanted gains during the cooling season, reduced overall gains by an average of 75%.


Energies ◽  
2021 ◽  
Vol 14 (13) ◽  
pp. 3874
Author(s):  
Rongda Ye ◽  
Xiaoming Fang ◽  
Zhengguo Zhang

The thermal performance of a phase change energy storage building envelope with the ventilated cavity was evaluated. CaCl2·6H2O-Mg(NO3)2·6H2O/expanded graphite (EG) was employed to combined with the building for year-round management. The energy consumption caused by the building under different influence parameters was evaluated numerically. The results indicated that CaCl2·6H2O-8wt %Mg(NO3)2·6H2O/EG should be installed on the south wall for the heating season, while CaCl2·6H2O-2wt %Mg(NO3)2·6H2O/EG should be integrated on the roof for the cooling season. When the air layer was ventilated and the south wall was coated with the solar absorbing coating, the room could save approximately 30% of energy consumption. Moreover, the energy consumption increased with an increase in the air layer thickness, and the air layers played a different role in the building envelope. The optimal value of the flow rate between air layer 2, air layer 3, and the room was 0.09 m3/s. To reduce the energy consumption, the phase change materials (PCMs) with large and small thermal conductivity should be installed in the south wall and roof, respectively. In general, the phase change energy storage building envelope with the ventilated cavity can save energy during the heating and cooling seasons.


2020 ◽  
Vol 36 (01) ◽  
pp. 14-40
Author(s):  
Michael G. Morabito ◽  
Bob Brier ◽  
Stuart Greene

The Cheops Boat is the most complete, largest, and one of the oldest boats ever excavated, but it has received surprisingly little study by Naval Architects. The 43-m boat was constructed around 2500 BC and placed, disassembled, in a pit next to the Great Pyramid at Giza in Egypt. Since its discovery in 1954, there has been speculation about its original design, means of propulsion, and purpose. This article presents previously unpublished results of the first tank testing of a model of the Cheops Boat and some preliminary conclusions about the design, propulsion, and function of the original. It is shown that the stability characteristics of the boat make it suited for carrying lightweight cargo and people in the protected waters of the Nile. Towing tests have shown that the boat can be safely rowed in a variety of wind and current conditions. Windward sailing calculations have shown that, if fitted with sail, then boats such as the Cheops Boat perform well downwind, but sail no closer than a beam reach. During the 1954 clearing of debris from the Giza Plateau, it was noticed that the Great Pyramid's north and west enclosure walls were 23.6m from the base of pyramid, but the south wall was 5mcloser to the base. Careful inspection revealed that the south wall had been built in an asymmetrical location to conceal two boat pits beneath it. The two pits were end to end, one covered by 41 massive limestone blocks and the other by 40. When the eastern pit was opened, the remains of the disassembled boat were revealed. Figure 1 shows photographs of some of the pieces as they were removed from the pit. Remarkably, the 4500-year-old cedar had been so well preserved that it was possible to reassemble this boat like a kit. Even the rope was preserved, and looked like what could be bought today.


2013 ◽  
Vol 368-370 ◽  
pp. 1250-1253
Author(s):  
Jia Yin Zhu ◽  
Bin Chen

Optimization design of building envelope-integrated collectors plays an important role in reducing energy consumption and improving thermal comfort. Take a passive solar house for an example, optimization design principles for passive solar house were proposed by simulation. Simulation results by changing envelope insulation thickness showed that the optimal thickness was between 30mm and 70mm for south wall, and 70mm~150mm for other façade, respectively. Meanwhile, the optimal thickness for concrete exterior walls was in the range of 200mm~300mm. Simulation of changing heat capacity proportion showed that the daily temperature difference decreased by 14oC to 5.2oC as the proportion increased doubled. However, considering the building initial investment, the arrangement of thermal mass should be determined by the building type and energy demand.


1929 ◽  
Vol 19 (1) ◽  
pp. 67-87 ◽  
Author(s):  
Jocelyn Toynbee

The paintings in the triclinium of the Villa Item, a dwelling-house excavated in 1909 outside the Porta Ercolanese at Pompeii, have not only often been published and discussed by foreign scholars, but they have also formed the subject of an important paper in this Journal. The artistic qualities of the paintings have been ably set forth: it has been established beyond all doubt that the subject they depict is some form of Dionysiac initiation: and, of the detailed interpretations of the first seven of the individual scenes, those originally put forward by de Petra and accepted, modified or developed by Mrs. Tillyard appear, so far as they go, to be unquestionably on the right lines. A fresh study of the Villa Item frescoes would seem, however, to be justified by the fact that the majority of previous writers have confined their attention almost entirely to the first seven scenes—the three to the east of the entrance on the north wall (fig. 3), the three on the east wall and the one to the east of the window on the south wall, to which the last figure on the east wall, the winged figure with the whip, undoubtedly belongs.


2008 ◽  
Author(s):  
Shiro Ueno ◽  
Dmitry Khrustalev ◽  
Peter Cologer ◽  
Russ Snyder

Sign in / Sign up

Export Citation Format

Share Document