A Procedure for Testing the Ability of Whole Building Energy Simulation Programs to Thermally Model the Building Fabric

1995 ◽  
Vol 117 (1) ◽  
pp. 7-15 ◽  
Author(s):  
R. D. Judkoff ◽  
J. S. Neymark

A procedure was developed for systematically testing whole building energy simulation models and diagnosing the sources of predictive disagreement. Field trials of the method were conducted with a number of detailed state-of-the-art programs by researchers from nations participating in International Energy Agency (IEA) Task 12 and Annex 21. The technique consists of a series of carefully specified test case buildings that progress systematically from extremely simple to relatively realistic. Output values for the cases, such as annual loads, annual maximum and minimum temperatures, peak loads, and some hourly data are compared, and used in conjunction with diagnostic logic to determine the algorithms responsible for prediction differences. The more realistic cases, while geometrically simple, test the ability of the programs to model such combined effects as thermal mass, direct solar gain windows, window shading devices, internally generated heat, infiltration, sunspaces, earth coupling, and deadband and setback thermostat control. The more simplified cases facilitate diagnosis by allowing excitation of particular heat transfer mechanisms. The procedure was very effective at revealing bugs, faulty algorithms, and input errors in a group of building energy simulation programs that may be considered among the world’s best. The output data from the simulation programs can be used as reference ranges for comparing and diagnosing other detailed or simplified design tools.

Energies ◽  
2020 ◽  
Vol 13 (16) ◽  
pp. 4058
Author(s):  
Matt S. Mitchell ◽  
Jeffrey D. Spitler

This paper presents an enhanced vertical ground heat exchanger (GHE) model for whole-building energy simulation (WBES). WBES programs generally have computational constraints that affect the development and implementation of component simulation sub-models. WBES programs require models that execute quickly and efficiently due to how the programs are utilized by design engineers. WBES programs also require models to be formulated so their performance can be determined from boundary conditions set by upstream components and environmental conditions. The GHE model developed during this work utilizes an existing response factor model and extends its capabilities to accurately and robustly simulate at timesteps that are shorter than the GHE transit time. This was accomplished by developing a simplified dynamic borehole model and then exercising that model to generate exiting fluid temperature response factors. This approach blends numerical and analytical modeling methods. The existing response factor models are then extended to incorporate the exiting fluid temperature response factor to provide a better estimate of the GHE exiting fluid temperature at short simulation timesteps.


Sign in / Sign up

Export Citation Format

Share Document